No Ac Call Back? Compressor not Running
I am on a no air-conditioning service call which is a potential call back. I was just working on this unit almost a month and a half ago. The contactor ended up breaking and I replaced it. Now the call is that the unit is not cooling, and the compressor is not running. I start checking out the unit and the side to test the capacitor. The capacitor tested good last time I was working on the unit. Yet this time the compressor side tested 0 µF, and the condenser fan side tested at 4.8 µF. I replaced the capacitor and the compressor start it up. At first, the superheat was really Hi about 40°. The suction pipe was really warm about 80 degrees. The temperature inside the house was also really warm about 93°. This is why the superheat was high and the suction pipe temperature was also high. I gave it some time and the superheat ended up dropping down to about 12° of superheat and the suction pipe was about 50 degrees at the end. The system will most likely be replaced by the end of the summer.
Видео No Ac Call Back? Compressor not Running канала The HVAC Hacker
Видео No Ac Call Back? Compressor not Running канала The HVAC Hacker
Показать
Комментарии отсутствуют
Информация о видео
Другие видео канала
One AC Not Cooling On Hot Days Other HVAC system cooling Multiple HVACCompressor Won’t Run DiagnosisWhy Do Capacitors Fail? (It’s not why you think)HVAC No Cooling Service Call WORST HELICOPTER EVER !!Home A/C Compressor Not Running - FixedAC Blown Fuse Low Voltage ShortHVAC: NO COOLING CALLHow to Check AC Freon Level No TOOLSAMERICAN STANDARD AC NOT RUNNINGLENNOX NO COOLING CALLSunday hvac no Cooling service callHVAC Service System Head Pressure Fault Multiple Problems RepairedNo power, eliminating all variables before finding problem.Burnout Compressor change (R410a) with acid cleanup3 calls, a day in the life of an HVAC tech…per requestTop 5 AC Problems and How to Fix ThemHVAC Service Call | Clogged PistonAC Compressor Open Windings Outdoor Unit Won’t StartDIY Hack Butcher HVAC Unit Sabatage by HomeownerTrane Heat Pump TXV valve replaced with my new helper