Second Generation Woodward 505 Direct Entry Valve Stroking
The Woodward manual(s) are pretty clear how to enter valve stroke mode, but it leaves the user only being able to move the valve incrementally with the Adjust ("ADJ") arrow key. This allows an exact valve percentage to be entered. A warning but an obvious one is when a value is entered, the control will step (not ramp) the valve actuator output to this value.
IMPORTANT: As for any valve stroking with a second generation 505, the Emergency Stop discrete input (terminal 12) must be energized throughout this procedure. In many cases, this requires installing a temporary jumper.
Видео Second Generation Woodward 505 Direct Entry Valve Stroking канала Karl Gubert
IMPORTANT: As for any valve stroking with a second generation 505, the Emergency Stop discrete input (terminal 12) must be energized throughout this procedure. In many cases, this requires installing a temporary jumper.
Видео Second Generation Woodward 505 Direct Entry Valve Stroking канала Karl Gubert
Показать
Комментарии отсутствуют
Информация о видео
Другие видео канала
WOODWARD 505 GOVERNOR || KEY FUNCTION OF WOODWARD 505E GOVERNOR || [हिंदी]Woodward 505 Part #1Triveni steam turbines 505 woodward governer view electronic governer 504Turbine thrust bearing 교체How to test an OVERSPEED SHUTDOWN ALARM of an Auxiliary Generator?control valve prosesDirect Acting Control Valve Bench Set AdjustmentESDV - Partial Stroke Testing(PST)Woodward Make 505 Turbine Controller With Turbine Technical Data || Industrial Vlogs 2021process main stop valve steam turbine23MW TURBINE highlights chlik this video and see thatWoodward Governor 505XTARS 60 MW SHIN NIPPON TURBINE OVERHAUL AND REFINNINGIni dia rahasia penting pada mesin CumminsWoodward 505Woodward 505 (third generation) Valve Output StrokingWhat is DCS Control System? | Distributed Control System Architecture | 2021Performing Factory Reset on Altistart 48 | Schneider Electric SupportTesting for Woodward DPG2201505 Configuration/Calibration - Actuator Drivers