Consider a two-stage cascade refrigeration system
operating between the pressure limits of 0.8 and 0.14 MPa.
Each stage operates on the ideal vapor-compression refrigeration
cycle with refrigerant-134a as the working fluid.
Heat rejection from the lower cycle to the upper cycle takes
place in an adiabatic counterflow heat exchanger where both
streams enter at about 0.4 MPa. If the mass flow rate of the
refrigerant through the upper cycle is 0.24 kg/s, determine
-(a) the mass flow rate of the refrigerant through the lower cycle,
-(b) the rate of heat removal from the refrigerated space
and the power input to the compressor, and
-(c) the coefficient of performance of this cascade refrigerator.
This video is for a Thermodynamics class
Mechanical Engineering
Problem: 11-56
Textbook : Thermodynamics an engineering approach, Yunus A Cengel, 8th Edition
If you would like to support the channel please take a look at my T-shirt designs:
https://www.teepublic.com/t-shirt/64574315-shifter-logo-with-funny-speeding-jail-reminder?store_id=464110
Thank you!
Видео Consider a two-stage CASCADE refrigeration system operating between the канала Engel Universe
https://www.youtube.com/channel/UCeBPT5Sx8Gx-doXhZA2AOoQ/store
Thank you !!!
Consider a two-stage cascade refrigeration system
operating between the pressure limits of 0.8 and 0.14 MPa.
Each stage operates on the ideal vapor-compression refrigeration
cycle with refrigerant-134a as the working fluid.
Heat rejection from the lower cycle to the upper cycle takes
place in an adiabatic counterflow heat exchanger where both
streams enter at about 0.4 MPa. If the mass flow rate of the
refrigerant through the upper cycle is 0.24 kg/s, determine
-(a) the mass flow rate of the refrigerant through the lower cycle,
-(b) the rate of heat removal from the refrigerated space
and the power input to the compressor, and
-(c) the coefficient of performance of this cascade refrigerator.
This video is for a Thermodynamics class
Mechanical Engineering
Problem: 11-56
Textbook : Thermodynamics an engineering approach, Yunus A Cengel, 8th Edition
If you would like to support the channel please take a look at my T-shirt designs:
https://www.teepublic.com/t-shirt/64574315-shifter-logo-with-funny-speeding-jail-reminder?store_id=464110
Thank you!
Видео Consider a two-stage CASCADE refrigeration system operating between the канала Engel Universe
Показать
Комментарии отсутствуют
Информация о видео
Другие видео канала
0.75 kg of water that is initially at 0.5 MPa and 30 percent quality occupies a spring-loaded pistonMustang Mach-E Tire pricesy^4y'=x+1. Solve the differential equation.Femap Nastran planar truss setup with 3 elements; merge nodes; results magnificationCFD animation for external flow over a square blunt body (velocity plot)Defective matrix System of ODE - algebraic multiplicity 3 while geometric multiplicity of 2x+6=2(x-3) Solve the Linear EquationEstimate the daily load and the peak power required by a PV system that have the following equipmentNatural convection from a heated cylinder Ansys animationInconsistent system of equationsA 5-ft3 rigid tank contains a saturated mixture ofrefrigerant-134a at 50 psiaWater is being heated in a vertical piston–cylinder device. The piston has a mass of 40 kgSimplify the logarithm - example. Product propertyKnotts Berry Farm balloon ride for kidsIn an experiment a gun is shot straight upward in a vertical fashionAn ideal gas undergoes two processes in a piston-cylinder device as follows:1-2 Polytropic compressiFemap Nastran Displacement controlled loadingFEMAP Nastran Loads and ConstraintsSimplify the expression. Combine rational expressionsA PV battery system has an end-to-end efficiency of 77%. The system is used to run an all-AC loadVolumetric flow rate between two parallel plates with one plate as fixed and one is moving