HVAC Troubleshooting Heat Gas Valve Failure Lockout
I am a HVAC service Tech on a no heat service call. The HVAC system locks out on a gas valve failure. I find the HVAC RTU's heat draft inducer motor running, blowing cold air out exhaust. First, I reset the heating system fault. Allowing the heat to go through its sequence of operation. The inducer motor turns on, the pressure switch closes, ignitor sparks, and burners light. Since everything works, I need to dig deeper into how everything operates. Next, I test the flame signal, then the electric energizing the gas valve. After a few tests, I realize that rust prevents the flame signal to the ignition module. Therefore I clean the flame sensor and wire connectors—the flame signal increases without interference.
Видео HVAC Troubleshooting Heat Gas Valve Failure Lockout канала The HVAC Hacker
Видео HVAC Troubleshooting Heat Gas Valve Failure Lockout канала The HVAC Hacker
Показать
Комментарии отсутствуют
Информация о видео
Другие видео канала
Goodman Gas Furnace Troubleshoot and replace gas valveBoiler Leaky Air Vent RepairCarrier RTU not heatinggas furnace will not fire29 year old Carrier Heat Exchanger ReplacementGas Furnace Spark Ignition Control Troubleshooting!HVAC No Cooling CallCarrier package unit not heatingSunday Call - No Power Anywhere !Old Gas Furnace Burner ServiceNo Heat Burners Won't LightHVAC-R VLOG / BE CAREFUL OUT THERENo Heat HVAC Service Call gas furnace power vent motor not provingMIND-BLOWING HOMEMADE PROJECTS YOU SHOULD SEEHeat Burner Not Igniting Inducer Starts HVAC troubleshootingMeasuring & Adjusting Furnace Gas Pressure X2THE WALK IN FREEZER IS TOO WARMgas furnace will not heat houseNew AC Ain’t Cooling