Worcester Greenstar - How To Test & Change The Flow Turbine | Boiler Not Getting A Demand On Water?
HOW TO TEST THE FLOW TURBINE:
In the video you will see there are 3 different coloured wires coming from the flow turbine, we will need to test all of them.
The 3 colours:
Black
Yellow
Red
1) Check between black and yellow without the tap running. You should be getting 5V or 0V DC.
2) Check between yellow to red without tap running. You should be getting 5V or 0V Dc
3) Check between red and black without tap running. You should have 5V DC.
Now with the hot tap running
4) Check between black and yellow. You should be getting 3.5-1.5V DC.
5) Check between yellow and red. You should be getting 3.5-1.5V DC.
6) If it’s still at 5V or 0V with the tap running, then the flow turbine is faulty. It should change when it detects water flowing through it, if the readings don’t change then it’s faulty.
*Note* Make sure you are also getting the correct flow rate for the boiler
Видео Worcester Greenstar - How To Test & Change The Flow Turbine | Boiler Not Getting A Demand On Water? канала Boiler Breakdown Training
In the video you will see there are 3 different coloured wires coming from the flow turbine, we will need to test all of them.
The 3 colours:
Black
Yellow
Red
1) Check between black and yellow without the tap running. You should be getting 5V or 0V DC.
2) Check between yellow to red without tap running. You should be getting 5V or 0V Dc
3) Check between red and black without tap running. You should have 5V DC.
Now with the hot tap running
4) Check between black and yellow. You should be getting 3.5-1.5V DC.
5) Check between yellow and red. You should be getting 3.5-1.5V DC.
6) If it’s still at 5V or 0V with the tap running, then the flow turbine is faulty. It should change when it detects water flowing through it, if the readings don’t change then it’s faulty.
*Note* Make sure you are also getting the correct flow rate for the boiler
Видео Worcester Greenstar - How To Test & Change The Flow Turbine | Boiler Not Getting A Demand On Water? канала Boiler Breakdown Training
Показать
Комментарии отсутствуют
Информация о видео
Другие видео канала
Flow Turbine adapter change on a Worcester BoschHow to test 3 wire flow sensors. Vaillant boiler no hot water. Combination Boiler. My first video.The dreaded Flow Switch - Potterton Promax/Baxi Solo/Main HeatFault Finding Using a MultimeterThe Bearded Plumber° Vaillant Flow Turbine Repairflow turbine adapterGas Training - How To Test Air Pressure Switches In Gas Boilers - Fault FindingMain Eco Elite | Changing The Diverter Valve & CartridgeWorcester Greenstar - How To Change / Replace The Return Manifold / Block / UnitWorcester Bosch 30si/28i junior flow adaptor replacementGas Training - Boiler Fault Finding - Baxi E110 / Main E1 10 - Roy FuglerCentral heating pump not workingLeaking Worcester Greenstar Flow Sensor/ Adaptor. Heating geeks boiler repairWorcester greenstar 24i junior boiler removal or new expansion vesselGas Training - Boiler Fault Finding - No Heat / No Hot Water Viva Training Academy Roy FuglerVaillant Ecotec | How To Put It Into Purge Program / P.00Worcester Bosch right hand block changeWorcester Bosch plate heat exchanger changeVaillant EcoTec Pro | F75 Fault Code | How To Change The Water Pressure SensorBaxi Duotec. 3 wire flow sensor testing. Baxi no hot water