Sizing Dryers and Ranges, Load Calculations
This video is to help you understand how to size a Dryer and a Range in a single family service calculation.
DRYER
Art. 220.54 States that a dryer must have a minimum demand of 5000 watts or the Nameplate rating which ever is greater.
RANGE
Art. 220.55 States that an electric range must be calculated according to Table 220.55
Note 1 is explained that if you have a range that is over 12kw every 1kw over 12kw must be calculate by 5%.
Example
15kw
-12kw = 3kw
3kw
x.05 = 15%
8000 per 220.55
x1.15 = 9200watts
Видео Sizing Dryers and Ranges, Load Calculations канала Craig Michaud- Electrical Instructor
DRYER
Art. 220.54 States that a dryer must have a minimum demand of 5000 watts or the Nameplate rating which ever is greater.
RANGE
Art. 220.55 States that an electric range must be calculated according to Table 220.55
Note 1 is explained that if you have a range that is over 12kw every 1kw over 12kw must be calculate by 5%.
Example
15kw
-12kw = 3kw
3kw
x.05 = 15%
8000 per 220.55
x1.15 = 9200watts
Видео Sizing Dryers and Ranges, Load Calculations канала Craig Michaud- Electrical Instructor
Показать
Комментарии отсутствуют
Информация о видео
31 мая 2018 г. 14:30:01
00:10:16
Другие видео канала
Table 220.55 Calculating the Range DemandSizing Heat & AC, Load CalculationBox Fill Calculations with New 2020 NEC Changes in Grounding Fill 314.16 (B) (5)Sizing Fixed Appliances, Load Calculations25 Electrical Exam Prep Practice Test Questions with full explanations VOL 1 MORE VOLUMES IN DESCRIPFinding General Lighting Load for DwellingsHow to Look up Answers in the Code Book FAST!! 3 MethodsWhy is there more than 200 A worth of breakers inside of a 200 amp panel?!Derating of Conductors ExplainedNEC Table 220.55Installing a GFCI Circuit BreakerTest Taking Tips for your Electrical Journeyman ExamEverything you need to know to solve Voltage Drop Calculations!!Basic understanding how a Holding relay wiredHere'$ Your Change - In the 2020 NECHow to complete a Load CalculationConduit Fill / Different Insulation typesCONDUIT FILL EXAMPLES for the Modern Electrician - How Many Conductors Can I Put In...