Siemens PLC S7-200 Smart ATO GK3000 VFD Modbus RTU Motor Control (Start/Stop ,Frequency)

In this video, I will show you how to control a motor using Siemens S7-200 Smart PLC with ATO GK3000 VFD via Modbus RTU (RS-485 communication).
🔧 Topics covered:
- Wiring S7-200 Smart PLC to GK3000 VFD
- Modbus RTU communication setup
- Start/Stop motor control (Run command)
- Frequency (speed) control from PLC
- Parameter settings for ATO GK3000 VFD
⚙️ Important Modbus Registers:
Start/Stop Control: 408193 (Send 1=Start, Send 6=Stop)
Frequency Setpoint: 420481, (Send 1000=10Hz, 2000=20Hz,....., 5000=50Hz)
🛠 Tools used:
- Step 7 MicroWin Smart V2.7
- WinCC RT Flexible 2008 SP5 or TIA Portal WinCC Advanced RT

👍 If this helps you, don't forget to Like & Subscribe for more PLC tutorials!